Key takeaways in 30 seconds
- The rating and type of protection depend on the circuit, cable, load, and installation conditions, not on the wall material.
- A combustible structure increases the importance of protection against thermal effects (AFDD, correct cross-section, careful connections), but does not exempt from calculations.
- Each device performs a different function: the overcurrent breaker protects the cable, the residual current device reacts to leakage, the AFDD detects arcs, and the SPD protects against surges.
- Lightning and surge protection result from a risk assessment, not from the combustibility of the building itself.
Why wood changes priorities, not the numbers on the devices
The consequence of an electrical fault is often heat: a smouldering connection or an arc in a loose wire. In a non-combustible house, it usually remains a local damage; in a wooden one, it comes into contact with material that can catch fire. Therefore, the importance of protection against thermal effects, cable selection, and connection quality increases - but not "higher settings". An overcurrent circuit breaker, "eska" (MCB, protecting the cable against overload and short circuit), is selected so that its rated current does not exceed the continuous current-carrying capacity of the cable (Iz), i.e., the current that the cable can withstand without overheating - identically in a brick and a wooden house.
What selection really depends on
The selection of protection and cable is the result of several factors: conductor cross-section and material, installation method, ambient temperature, proximity to thermal insulation, cable grouping, circuit length, loop impedance (Zs, i.e., the impedance of the path through which the fault current flows), load characteristics, and selectivity. In a wooden house, cables run in thermal insulation are key: they dissipate heat less effectively, so their current-carrying capacity drops. The wiring selection standard (PN-HD 60364-5-52) requires correcting the calculated Iz with temperature and grouping factors - with full insulation surrounding, they can be around 0.5. Conclusion: sometimes a thicker cable or a different route is needed, not a change of fuse.
Each device has a different function
Several devices cooperate in the distribution board, and they do not replace each other. An overcurrent circuit breaker (MCB) protects the cable against overload and short circuit. A residual current device (RCD) reacts to earth leakage; a level up to 30 mA provides additional protection to protect people, and an RCBO combines both functions. An AFDD detects an arc (e.g., in a loose connection) that standard protections might not recognise. A surge protective device (SPD) diverts surge energy, and the main switch disconnects the installation for maintenance work and is not the same as the fire safety switch required in larger facilities. They are complemented by earthing and equipotential bonding, as well as division into circuits to limit the scope of a failure.
The standard for protection against thermal effects (PN-HD 60364-4-42, with the 2015 amendment, former clause 421.7) recommends AFDDs, among others, in combustible buildings - this is a standard recommendation, not a legal obligation; Polish technical conditions do not mandate AFDDs. The international edition IEC 60364-4-42:2024 was published with expanded provisions on AFDDs (clause 426), but it has not yet been implemented in Poland as PN-HD, so it does not create an obligation here. The application is decided by the designer together with the investor; sometimes it is required by the developer's specification or appreciated by the insurer.
Lightning protection, surges, and large loads
The need for a lightning protection system (LPS, a system capturing direct lightning strikes) results from a risk analysis according to PN-EN 62305, and not from the combustibility of the building itself. Similarly, a surge protective device is selected according to an exposure assessment (PN-HD 60364-4-443), and in areas with overhead power supply, the condition usually points to an SPD. "Wooden, so lightning protection and surge protection are mandatory" is a simplification - the basis is the assessment, not the wall material.
Additional sources and large loads (photovoltaics, energy storage, heat pump, charger) change the selection picture: a residual current device reacting to DC currents and separate circuits may be needed - this is a topic for the design stage.
Connection quality, measurements, and documents
In a combustible house, careful and inspected connections are of particular importance, as connections are where heating most often occurs. Before commissioning, the installation requires initial verification according to PN-HD 60364-6: inspection and testing (including continuity of the protective conductor PE, insulation resistance, loop impedance, RCD operation) and a measurement report. Later, it is subject to periodic inspection of technical condition, at least once every 5 years in accordance with the Prawo budowlane (Building Law). Your role starts earlier: provide the designer with the loads and their power ratings, plans for PV, storage, heat pump or charger, as well as the type of insulation and routes. After completion, you receive the complete set: as-built documentation, measurement reports, and distribution board description.
Table: what protects against what and what it does not replace
| Design element / protection | What phenomenon it protects against | What selection depends on | What it does not replace |
|---|---|---|---|
| Miniature circuit breaker (MCB) | Cable overload and short circuit | Cable cross-section and current-carrying capacity (Iz), Zs, short-circuit current, load characteristics | Residual current protection or AFDD |
| RCD up to 30 mA | Effects of leakage (additional protection for people) | Circuit type, AC/A/F/B type according to loads, network system | Basic protection or overcurrent protection |
| RCBO | Leakage + overload and short circuit in one module | As for MCB and RCD combined | AFDD or surge protection |
| AFDD | Specific arcing phenomena (risk of ignition) | Facility risk, standard recommendation, design decision | MCB, RCD, SPD or correct connections |
| Surge protective device (SPD) | Atmospheric and switching surges | Risk assessment (4-443), installation location, type 1/2/3 | Lightning protection system or earthing |
| Main switch-disconnector | Disconnecting the installation for work (isolation) | Network system, current, selection standard 5-53 | Overcurrent protection or fire safety switch |
| Earthing and equipotential bonding | Dangerous potential differences | Network system, soil conditions, measurements | Automatic disconnection of supply or overcurrent protection |
| Lightning Protection System (LPS) | Effects of direct lightning strikes | Risk assessment according to PN-EN 62305 | Surge protective devices inside the installation |
Most common misunderstandings
"In a timber house, always use a 300 mA RCD." The 300 mA level limits the risk of fire from leakage currents, but does not protect against electric shock - humans are protected by levels up to 30 mA. These are two different functions, and the values result from the design.
"AFDD is strictly mandatory in every timber house." In Poland, AFDD is a standard-recommended measure for combustible structures, not a legal obligation. It is highly sensible in such a house, but the decision depends on the building assessment, not an automatic rule.
"Just downsize the fuse to make it safer." A rated current that is too low causes nuisance tripping and does not fix an incorrectly sized cable. Selection is about coordinating the device with the cable and short-circuit conditions, not a "smaller number".
"Every cable must be halogen-free." Halogen-free (LSZH) cables are sometimes justified, but this depends on the building conditions and reaction-to-fire classification, not the flammability of the walls itself. This is a design decision for specific routes, not a rule for every cable.
When should you ask an electrician to check the installation?
Arrange an inspection and testing if you notice symptoms: a burning smell near sockets and in the distribution board, signs of melting, sparking, a warm device casing, or repeated tripping of a single circuit. If you smell burning or see smoke and can do so without touching the damaged component, turn off the circuit power supply and call a professional. Do not open the distribution board, do not remove covers, do not replace devices or fuse links, and do not carry out repairs yourself. A plan for expansion (PV, battery storage, heat pump, EV charger) and the approaching date of a periodic inspection are also reasons for a discussion. The TEST button on the RCD only confirms the mechanical operation, it does not replace testing.
Summary
A timber house does not have its "own" protection rating value: a combustible structure increases the importance of protection against thermal effects and the quality of connections, while the selection of each device depends on the circuit, cable, load, and installation conditions. Decisions on AFDD, lightning protection, and surge protection are based on risk assessment, not on the slogan "because it is timber", and the whole process is completed by careful installation, testing, and a full set of documents.
Want to be sure? We carry out installation inspections, initial and periodic testing, and verification of protective device selection in terms of circuits and loads. Planning photovoltaics, energy storage, a heat pump, or an EV charger? We will check how they affect the choice of protection and prepare a documented condition assessment with clear recommendations. Order an inspection with testing: book a visit online or call +48 459 566 991.
FAQ: frequently asked questions
Do timber houses require thicker cables than brick houses?
Not because of the wood itself, but because of the installation conditions. Cables routed in thermal insulation dissipate heat less effectively, so their current-carrying capacity decreases and the selection standard requires calculations to be adjusted. In practice, this sometimes means a larger cross-section or a different route, determined by calculations.
Will an AFDD replace my RCD and fuses?
No. An AFDD detects specific arc faults. It does not react to earth leakage (which is the RCD's job) nor does it protect the cable against overload and short circuit (which is the circuit breaker's job). These devices complement each other.
Does a timber house always require a lightning protection system?
Not automatically. The need for and class of a lightning protection system is determined by a risk assessment according to PN-EN 62305. Flammability is one of the factors that increases fire risk, but it does not decide on its own.
Is a surge protective device mandatory in my house?
This depends on the exposure assessment according to the selection standard, not on the wall material. In areas with overhead power lines, the condition often indicates the need for an SPD; the final selection of type and installation location is made by the designer.
What should I receive from the contractor after the work is completed?
As-built documentation, initial verification test reports, and a clear description of the distribution board with circuit labels. This is a complete set that allows you to safely operate the installation and plan future work.
I have an old installation with rewirable/cartridge fuses - does that mean it is dangerous?
The type of protection itself does not determine a defect. The risk usually arises from incorrect selection, modifications, or wear and tear, which is confirmed by inspection and testing. Read more in a separate post about old fuses.
Sources and legal basis
Verification date: 18 July 2026.
- Prawo budowlane (t.j. Dz.U. 2026 poz. 524, obwieszczenie z 27.03.2026) - art. 62 ust. 1 pkt 2, okresowa kontrola instalacji elektrycznej co najmniej raz na 5 lat
- PKN - PN-HD 60364-4-42:2011 oraz PN-HD 60364-4-42:2011/A1:2015-01 - Ochrona przed skutkami cieplnymi (AFDD)
- IEC - IEC 60364-4-42:2024 - Low-voltage electrical installations. Protection against thermal effects (Edition 4.0)
- PKN - PN-HD 60364-5-52:2011 - Dobór i montaż wyposażenia elektrycznego. Oprzewodowanie
- PKN - PN-HD 60364-6:2016-07 - Sprawdzanie (odbiory i badania okresowe)
- elektro.info - Projektowanie instalacji odgromowych według PN-EN 62305
- RST - Dobór ograniczników przepięć w instalacjach elektrycznych według znowelizowanych norm PN-HD 60364
- Grodno - Fire-resistant and halogen-free cables - when are they mandatory (CPR / EN 50575)



